Inclination sensor JN
21
10.8 MEMS measuring cell temperature (0x2081)
The temperature of the measuring cell is determined every 200 ms and updated
in the protocol at "informative"� It can be read via access to the index 2081h� The
signed 16-bit value indicates the temperature in 1/10°C�
10.9 MEMS self-test (0x4008 / 0x4009)
To check the function of the measurement axes a self-test of the measuring cell
can be carried out�
The MEMS self-test (index 4008/01h) has to be activated by writing the value
1� The self-test takes about 2 s; when the self-test has ended, the flag (index
4008/01h) is reset to 0� The test result is coded in a byte and can be read from the
self-test register (index 4009h)�
00000111 of the 3 least significant bits code the internal X, Y, Z measurement
axes: axis faulty / bit 1: axis functional
10.10 Programming key (0x3000)
The sensor can convert the parameter setting unambiguously into a Base64-coded
key
By means of this key sensors with the same parameter setting can be duplicated
in an easy way
The programming key can be read from and written to index 3000h� To ensure
that only valid keys are accepted by the firmware a 2-byte checksum (CRC) is
calculated and added to the end of the key
The following parameters are coded by the key
Parameter Index Sub-index
Node ID 0x2000 0x00
Baud rate 0x2001 0x00
Quadrant correction 0x2040 0x00
Heating 0x2041 0x00
Teach index 0x2042 0x00
FIR filter angle 0x2043 0x00
Angle calculation 0x2044 0x00
CAN 120 Ohm resistor 0x2045 0x00
Set zero point 0x2046 0x00
Output value 0x2047 0x00
Axis selection for Veff & aPeak 0x2048 0x00
FIR filter for vibration measurement 0x2049 0x00
Measuring range vibration measurement 0x204A 0x00