Device manual Profibus encoder RM30xx RN30xx706355/00 06/2013 UK

Page 2 - Contents

Encoder with Profibus interface109.2.3 Scaling functionThe scaling function enables parameter setting of the resolution per revolution and the select

Page 3

UKEncoder with Profibus interface11When the [Total measuring range] parameter is entered, use the following formula:total resolution < measuring st

Page 4 - 2 Safety instructions

Encoder with Profibus interface129.3.2 Preset functionThe preset function enables adaptation of the encoder zero point to the mechanical zero point o

Page 5 - 4 Functions and features

UKEncoder with Profibus interface1310 Profibus encoder profile Class 2Parameter setting telegramOctet (= byte) no. Parameters Bit no. Details1���8 Pr

Page 6 - 6 Installation

Encoder with Profibus interface1410.1 ParametersThe manufacturer-specific parameters are described below� The parameters to the encoder profile (also

Page 7 - 7 Installation

UKEncoder with Profibus interface1510.1.3 Required resolutionParameter selection of – resolution per revolution – or max� total resolution – code seq

Page 8 - 9 Encoder classes

Encoder with Profibus interface16Resolution per physical measuring stepsThe requested number of steps refers to the data entered via the [Physical imp

Page 9

UKEncoder with Profibus interface1710.1.5 Reduced diagnosisWith older Profibus masters the full number of diagnostic bytes (standard diagnosis: 57 by

Page 10

Encoder with Profibus interface1810.1.7 Physical measuring stepsOctet 35 36 37 38Bit 31���24 23���16 15���8 7���0Data 231���224223���216215���2827���

Page 11

UKEncoder with Profibus interface1910.1.9 Unit of measurement velocityThe unit for the velocity value to be provided (class ifm 2�2) can be set via t

Page 12

Encoder with Profibus interface2Contents1 Preliminary note � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Page 13 - Parameter setting telegram

Encoder with Profibus interface20The status bits in the input double word have the following meaningBit Meaning 28 Rotational direction 0 = increasing

Page 14

UKEncoder with Profibus interface2110.3.1 Set the direction of rotationThe direction of rotation cannot be changed online in the set-up mode� The cur

Page 15 - Selection required resolution

Encoder with Profibus interface22Positive and negative direction of rotation and if the zero point is possible exceeded is considered automatically� T

Page 16

UKEncoder with Profibus interface2310.4.2 Preset valueThe preset value is set according to the procedure described in chapter 9�3�2� Only difference:

Page 17

Encoder with Profibus interface2411 Diagnostic messages11.1 OverviewIn the DDLM_Slave_Diag operating mode, diagnostic data is transferred from the e

Page 18

UKEncoder with Profibus interface2511.2 Supported diagnostic messagesThe individual diagnostic inputs are described in detail below�11.2.1 Extended

Page 19

Encoder with Profibus interface2611.2.6 Number of revolutionsThe physical number of the distinguishable revolutions per encoder can be enquired via t

Page 20

UKEncoder with Profibus interface2711.2.14 Serial numberAccording to the encoder profile, diagnostic bytes 48���57 are intended for a serial number�

Page 21

Encoder with Profibus interface2813 Configuring with STEP7In the following chapter the configuration of the ifm encoder with the configuration tool H

Page 22

UKEncoder with Profibus interface29Selecting the GSD file from the directoryAfter correct import and an update of the hardware catalogue via [Options]

Page 23 - 10.4.2 Preset value

UKEncoder with Profibus interface310�3�1 Set the direction of rotation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 2110�4 Start te

Page 24 - 11 Diagnostic messages

Encoder with Profibus interface3013.2 Adding an encoder to a STEP7 projectTo add an encoder to a project, the absolute encoder can be selected from t

Page 25

UKEncoder with Profibus interface3113.3 Parameter settingMark the encoder to be configured in projection and then doubleclick on location 1 (table in

Page 26

Encoder with Profibus interface41 Preliminary note1.1 Symbols used► Instruction> Reaction, result[…] Designation of keys, buttons or indications→

Page 27 - 12 LED indicators

UKEncoder with Profibus interface53 General information3.1 1.2 Profibus technology Profibus is a manufacturer-independent, open fieldbus standard de

Page 28 - 13 Configuring with STEP7

Encoder with Profibus interface65 Electrical connection ► Disconnect power� ► Connect the device according to the indications on the type label�5.1

Page 29

UKEncoder with Profibus interface77 InstallationThe encoder is connected via the terminal cap� It is connected to the encoder via a 15-pole D-Sub-con

Page 30

Encoder with Profibus interface8When the terminal resistor is activated, the next bus (Bus Out) is decoupled�The bus is only correctly connected if th

Page 31

UKEncoder with Profibus interface99.2 Parameter settingThe following table gives an overview of the parameters that can be set according to the encod